Weil-McLain · Boiler troubleshooting
Low water protection and external low water cut-off
What is going on
The U-Control uses a dual sensor in the heat exchanger for low water protection. Some jurisdictions require an external low water cut-off.
Likely causes
- Difference between the two heat exchanger sensors exceeds 10 °F
Check in this order
- The U-Control compares the two sensor readings and keeps them within 10 °F of each other.
- If the difference is more than 10 °F, the boiler shuts down on automatic reset.
- Where code requires, install an external low water cut-off as shown in the wiring diagrams.
- Where possible, use the Weil-McLain Ultra low water cut-off kit, which has a probe-type cut-off and a plug-in harness.
Applies to: Ultra low water protection
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 4 boiler manual, p. 95. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.