Viessmann · Boiler troubleshooting

Replacing the coding card or display and programming unit

Vitocrossal 300 CA3B

What is going on

Coding card and display replacement on the burner control unit.

Check in this order

  1. Disconnect KM-BUS connector.
  2. Undo the 2 mounting screws and tighten to 9 lb.in (1 Nm) on reinstall.
  3. Lift the display and programming unit and disconnect its connecting cable plug.
  4. Remove the display and programming unit.
  5. To change the coding card, pull it from the burner control unit and insert the new card.
  6. To change the display, install the new unit in reverse order.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.