Viessmann · Boiler troubleshooting

Check neutralization unit

Vitodens 200-W

What is going on

The granulate is used up as it neutralizes the condensate. The red mark shows the minimum fill level. A field-supplied pH strip is needed.

Likely causes

  • Condensate pH below 6.5
  • Contaminated granulate

Check in this order

  1. Check the condensate pH with a pH strip.
  2. If pH is below 6.5, replace the granulate.
  3. If the unit is contaminated, rinse it with tap water.
  4. Add granulate up to the red minimum fill mark.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service instructions, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.