Viessmann · Boiler troubleshooting
Boiler cleaning and flue gas check
What is going on
Rising flue gas temperature shows contamination or poor burner adjustment and reduces efficiency. A flue gas temperature sensor (accessory) can monitor this. The built-in hours run meter tracks burner operating time.
Likely causes
- Boiler contamination
- Incorrect burner adjustment
Check in this order
- Measure the flue gas temperature with a flue gas thermometer or the optional flue gas sensor.
- If the flue gas temperature is too high, clean the boiler.
- If needed, readjust the burner.
- Use the hours run meter to check burner operating times; longer run times mean lower standby losses (see VDI 2067 for guide values).
Applies to: Boiler and burner service
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 operating instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.