Boiler cleaning and flue gas check

Vitotronic 300

What is going on

Rising flue gas temperature shows contamination or poor burner adjustment and reduces efficiency. A flue gas temperature sensor (accessory) can monitor this. The built-in hours run meter tracks burner operating time.

Likely causes

  • Boiler contamination
  • Incorrect burner adjustment

Check in this order

  1. Measure the flue gas temperature with a flue gas thermometer or the optional flue gas sensor.
  2. If the flue gas temperature is too high, clean the boiler.
  3. If needed, readjust the burner.
  4. Use the hours run meter to check burner operating times; longer run times mean lower standby losses (see VDI 2067 for guide values).

Applies to: Boiler and burner service

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 operating instructions, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.