Solvent-weld PVC or CPVC vent and air joints
What is going on
Follow the pipe manufacturer's instructions for preparation and assembly.
Check in this order
- Deburr inside and outside of each pipe end.
- Chamfer the outside of each pipe end so cement spreads evenly.
- Clean all pipe ends and fittings and dry them thoroughly.
- Handle fittings and pipe carefully so the joint surfaces are not contaminated.
- Apply primer liberally to the pipe end and fitting socket.
- While the primer is still damp, apply cement in a uniform coat to both surfaces. Apply a second coat. Avoid excess cement in the socket.
- With cement still wet, insert the pipe fully into the fitting, twisting about 1/4 turn.
- Wipe off excess cement and check for a smooth bead all around the joint.
Applies to: ECO Tec Series 3 PVC/CPVC vent and air piping
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.