Reinstall heat exchanger cover plate, blower, burner and igniter after annual service

SVF 500/600 Series 1

What is going on

Reassembly order for the burner and cover plate after cleaning or inspection. Gas-tight sealing is critical.

Check in this order

  1. Set the cover plate on the heat exchanger with the blower flange facing front and square.
  2. Start all cover plate bolts by hand, then tighten in a star pattern with a 5 mm Allen wrench to 88 in-lbs.
  3. Set the blower, venturi and gas valve assembly in place, start the four nuts by hand, then torque to 88 in-lbs with a 13 mm wrench.
  4. Reconnect the flex gas line to the inlet pipe with two pipe wrenches and reconnect the blower harnesses.
  5. Fit a new burner gasket into the cover plate, install the burner and torque the six bolts in a star pattern to 44 in-lbs.
  6. Install the burner access hatch seal and access cover, then torque the five bolts to 44 in-lbs.
  7. Insert the ignition electrode with its gasket, start the two screws by hand, torque to 20 in-lbs, and reattach the igniter cable and ground wire.
  8. Reinstall the condensate trap on the heat exchanger drain and tighten the hose clamp.
  9. Check the ignition electrode, igniter gasket and cover plate seals are gas-tight before startup.

Applies to: SVF 500/600 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 112-113. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.