Viessmann · Boiler troubleshooting

Mount the outdoor temperature sensor

Vitotronic 300

What is going on

Mount the sensor on a north or north-west wall, 2 to 2.5 m (6.5 to 8 ft) above ground. On multi-storey buildings use the upper half of the second storey.

Check in this order

  1. Keep the sensor away from windows, doors, air vents, balconies and guttering.
  2. Do not paint over the sensor housing.
  3. Remove the cap and mount the bottom part of the sensor housing.
  4. Pull the sensor wire through the opening in the terminal compartment and through the strain relief.
  5. Connect the wires to the terminals.
  6. Refit the cap over the sensor.

Applies to: Outdoor temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 Installation and Service Instructions, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.