Viessmann · Boiler troubleshooting

Application Example 5 system layout

Vitotronic 300

What is going on

One direct-connected boiler circuit without a mixing valve, plus two mixing-valve heating circuits, with a DHW tank. The Vitotronic 300 runs the boiler, the DHW tank and both mixing circuits through the Power Pump Module and the KM-BUS expansion module. A supply check valve is needed only where the boiler return is piped as one common connection.

Check in this order

  1. Fit the Vitotronic 300 with the Power Pump Module and the KM-BUS expansion module.
  2. Connect mixing valve 1 and mixing valve 2 through their actuator accessory kits, with the supply sensor in each kit.
  3. Wire the DHW tank sensor and the DHW pumps to their connections.
  4. Fit a supply check valve only if the boiler return is one common connection.
  5. Connect the return water sensor only where the design needs it, for example underfloor heating that controls supply and return temperature.

Applies to: Application Example 5, Vitotronic 300 with two mixing-valve circuits

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 installation instructions, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.