Choose a vent termination location
What is going on
Termination clearances for concentric and twin pipe venting. Exact clearances are in the vent clearance setting. Local codes and the gas supplier can override these.
Check in this order
- Place all horizontal and vertical terminations at least 12 in (0.30 m) above grade or the anticipated snow level.
- Keep 60 in (1.52 m) between terminals at the same level and 60 in vertically between terminals at different levels.
- For twin pipe multi-boiler vertical venting, keep the exhaust at least 12 in (0.30 m) above the combustion air opening.
- Keep the combustion air intake out of the area marked as not permitted in the sidewall diagram.
- Check the clearance to windows, doors, air inlets, soffits, corners and walkways against the clearance setting.
Applies to: Concentric and twin pipe terminations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 37-38, 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.