Wire a boiler return mixing valve or isolation/modulating valve (CM2)
What is going on
Connect a 120 V or 24 V valve actuator for the CM2 boiler, using the 120 V L out supply.
Check in this order
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail inside the connection enclosure.
- Plug the gS plug into socket gS on the control.
- Secure the cable with a tie (see page 21).
- Connect the adaptor's black wire to the 120V L out connection on the DIN rail, terminals 10, 11 or 12.
- Connect the valve actuator wires to the adaptor terminals as shown in the figures.
Applies to: CM2 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.