Test the probe-type low water cutoff (steam)

Weil-McLain SGO Series 4

What is going on

Monthly check that the probe LWCO really stops the burner on low water.

Check in this order

  1. Turn power off and wait 5 minutes.
  2. Drain water down to the bottom of the gauge glass.
  3. Turn power on and call for heat. The red neon lamp on the LWCO should light.
  4. Wait 5 minutes. The burner must not fire.
  5. Refill to the normal water line. The red lamp should go out.
  6. Wait 5 minutes. The burner should fire.
  7. Set the thermostat back. If the burner fires with low water, the LWCO or its wiring is bad: fix before leaving the boiler running.
  8. Float-type LWCO blow down and test per the control maker. Only blow down if blow-down piping is installed (scald risk).

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Check monthly p.6; Check out procedure p.35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.