Existing common vent test when replacing a boiler

SVF 500/600 Series 1

What is going on

Required when removing a boiler from a common vent. The SVF must not use the existing common vent and needs its own vent and air piping. This test checks that the remaining appliances on the old common vent still vent properly.

Likely causes

  • Removing the boiler may leave the remaining appliances on an oversized common vent.

Check in this order

  1. Seal any unused openings in the common venting system.
  2. Inspect the venting system for proper size and horizontal pitch, and for blockage, restriction, leakage, corrosion or other defects.
  3. Close all building doors and windows where practical, and close doors between the appliance space and other spaces.
  4. Turn on the clothes dryer, any other appliance not on the common vent, and all exhaust fans except summer exhaust fans, at maximum speed. Close fireplace dampers.
  5. Light the appliance being tested and set the thermostat so it runs continuously.
  6. After five minutes of main burner operation, check for spillage at the draft hood relief opening using a match, candle or smoke.
  7. Test each remaining appliance separately with all other appliances off.
  8. Return doors, windows, fans, dampers and other gas appliances to their normal settings.
  9. If the common vent does not vent properly, correct it per NFPA 54 (or CAN/CSA B149.1 in Canada). Resize toward the minimum size from the code tables.

Applies to: Replacing an SVF boiler on an existing common vent

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.