Priority and input/output setup for multiple heat demands

SlimFit Series 3

What is going on

Each input is assigned a priority. The priority sets which system runs first and how long each may run.

Check in this order

  1. Assign Priority 1, 2 or 3 to each input in the WIZARD or ASSIGN INPUTS menu.
  2. Set the MAX ON TIME (longest a priority runs before a lower priority can call) and MIN ON TIME (shortest a priority runs before switching) for each priority.
  3. If inputs share a priority, they run together whenever that priority is active.
  4. Set Blr Circ to OFF for DHW piped directly with its own DHW circulator.

Applies to: SlimFit Series 3 single boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.