Install condensate trap and condensate line

SlimFit Series 2

What is going on

The condensate trap bolts to the boiler condensate outlet at the lower front center and its support foot sets the trap level. Use 1 in PVC or CPVC drain line with materials per the authority having jurisdiction. If a pump is used, select one approved for condensing boilers, fitted with an overflow switch, and powered from an external source.

Check in this order

  1. Remove the trap parts from the trim bag.
  2. Slip the flexible coupling over the trap outlet and tighten one hose clamp; leave the other loose until the line is installed.
  3. Insert the trap inlet gasket into the inlet ferrule.
  4. Slide the trap inlet onto the boiler condensate outlet and tighten the ferrule by hand.
  5. Extend the adjustable support foot to the floor so the trap is level.
  6. Run 1 in PVC or CPVC to a drain or condensate pump.
  7. If using a pump, confirm the overflow switch and external power.
  8. Size the pump for the total load of all connected boilers.

Applies to: SlimFit SF1000, SF1500, SF2000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 2 boiler manual, p. 44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.