Adjust low fire CO2 at the offset screw
What is going on
Set the low fire CO2 using the offset regulating screw under the 4mm cap.
Check in this order
- Set the boiler to LOW (minimum output) and let it stabilize.
- Check the blower rpm against the table in Figure 125, 126 or 127 (p. 145-147).
- Remove the 4mm Allen head cap (see Figure 120, p. 135).
- If CO2 is high, turn the offset screw counterclockwise to lower the input.
- If CO2 is low, turn the offset screw clockwise to raise the input.
- Let the boiler stabilize and read again. Repeat until the target CO2 is reached.
- Confirm CO is within limits.
- Reinstall the 4mm cap when adjustment is complete.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.