Viessmann · Boiler troubleshooting
Check condensate neutralization unit
What is going on
Check the condensate pH and refill the neutralization granulate. Field-supplied pH measuring strip required.
Likely causes
- Granulate is used up as it neutralizes condensate
- Condensate pH below 6.5
Check in this order
- Check condensate pH with a pH measuring strip.
- If pH is below 6.5, replace the granulate.
- If the unit is contaminated, rinse it with tap water.
- Refill granulate up to the red minimum-fill mark.
Applies to: Neutralization unit (if installed)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.