Viessmann · Boiler troubleshooting

Check condensate neutralization unit

Vitodens 200-W B2HA

What is going on

Check the condensate pH and refill the neutralization granulate. Field-supplied pH measuring strip required.

Likely causes

  • Granulate is used up as it neutralizes condensate
  • Condensate pH below 6.5

Check in this order

  1. Check condensate pH with a pH measuring strip.
  2. If pH is below 6.5, replace the granulate.
  3. If the unit is contaminated, rinse it with tap water.
  4. Refill granulate up to the red minimum-fill mark.

Applies to: Neutralization unit (if installed)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.