Weil-McLain · Boiler troubleshooting

Zoning three space heating zones plus indirect DHW piped to boiler

Evergreen ProSeries 2

What is going on

Layout for three space heating zones with an indirect DHW tank piped directly to the boiler. Shown for 110/155 models; 220-399 use the wiring diagram.

Check in this order

  1. Review the 120VAC output wiring and 24VAC input wiring pages (49 and 50).
  2. Wire the DHW aquastat to INPUT 1 (J17-1/2).
  3. Wire the space heating thermostats to INPUT 3 and INPUT 4, plus the third zone input.
  4. Assign INPUT 1 to PRIORITY 1 for DHW.
  5. Set System Settings 2, 3 and 4 to PRIORITY 2 and choose the space heating system type that matches the system, either in the WIZARD or in the PRIORITY 2 menu.
  6. Keep the factory default DHW and heating system settings, or change them if needed.
  7. Wire each circulator or zone valve to its matching output, at no more than 2.0 A per circulator.

Applies to: Evergreen Pro control, three space heating zones plus indirect DHW

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.