Weil-McLain · Boiler troubleshooting
Re-check maximum and minimum CO2 and CO
What is going on
Confirm the combustion settings at both high and low fire after adjustment.
Check in this order
- Turn the boiler off, then on again, and put it in Test Mode at maximum.
- Confirm the CO2 setting has not changed and CO is within limits.
- Reduce to minimum and re-check output, confirming CO2 is unchanged and CO is within limits.
- If CO2 and CO cannot be obtained, contact WM Technologies.
- Replace the test port cap (A), see Figure 118, p. 132.
Applies to: ECO Tec Series 3 gas boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.