Weil-McLain · Boiler troubleshooting
Boiler does not start
What is going on
Checklist from the start-up section when the boiler fails to light.
Likely causes
- Loose connection, blown fuse or service switch off
- Boiler temperature setting below boiler water temperature
- Thermostat set below room temperature
- Gas not turned on at the meter or boiler
- Incoming gas pressure too low (below 5 in. w.c. natural gas, or below 11 in. w.c. propane)
Check in this order
- Check for loose connections, a blown fuse or the service switch being off.
- Confirm the boiler temperature setting is above the boiler water temperature.
- Confirm the thermostat is set above room temperature.
- Confirm gas is on at the meter and at the boiler.
- Check incoming gas pressure at least 5 in. w.c. for natural gas or 11 in. w.c. for propane.
- If none of these fixes the problem, go to the troubleshooting section.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.