Weil-McLain · Boiler troubleshooting

Boiler does not start

CGi Series 5

What is going on

Checklist from the start-up section when the boiler fails to light.

Likely causes

  • Loose connection, blown fuse or service switch off
  • Boiler temperature setting below boiler water temperature
  • Thermostat set below room temperature
  • Gas not turned on at the meter or boiler
  • Incoming gas pressure too low (below 5 in. w.c. natural gas, or below 11 in. w.c. propane)

Check in this order

  1. Check for loose connections, a blown fuse or the service switch being off.
  2. Confirm the boiler temperature setting is above the boiler water temperature.
  3. Confirm the thermostat is set above room temperature.
  4. Confirm gas is on at the meter and at the boiler.
  5. Check incoming gas pressure at least 5 in. w.c. for natural gas or 11 in. w.c. for propane.
  6. If none of these fixes the problem, go to the troubleshooting section.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.