Mount the boiler on wall bracket or free-standing frame
What is going on
Install the wall bracket or stand first, then hang the boiler and level it. The B2HB has no mounting template, so the wall positions for the frame, bracket and vents must be calculated in the field. Boiler must be level both ways so condensate drains.
Check in this order
- Fasten the boiler stand or frame securely to the floor, using concrete anchors. Wall-fixing for the frame may also be needed.
- Attach the wall mounting bracket to the boiler mounting frame with the supplied hardware. Check that the bracket is level.
- Remove the external accessories connection box cover and loosen (do not remove) the bottom boiler screws.
- Remove the front enclosure panel by lifting it up and pulling it away from the boiler.
- Hang the boiler on the mounting bracket, make sure it is secure, and fit the holding bracket to the frame above the boiler.
- Adjust the levelling screws until the boiler is level vertically and horizontally.
- Connect the boiler to the installation fittings.
Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation manual, p. 16-17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.