Viessmann · Boiler troubleshooting
Single-boiler vs multi-boiler coding with external controls
What is going on
Set coding 01 for the system type. Multi-boiler systems need plugs aVD and aVH wired.
Check in this order
- Single-boiler system set coding 01: 1 (factory setting). With a building automation system, only plug aVD is required.
- Set boiler water temperature to the minimum value.
- Multi-boiler system set coding 01: 3.
- Wire both plugs aVD and aVH. DHW tank and load-dependent cascade control must run through the building automation system.
- The boiler activation contact is essential. The lead boiler contact must stay constantly closed.
Applies to: Single and multi-boiler systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, GC1 installation manual, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.