Viessmann · Boiler troubleshooting

Single-boiler vs multi-boiler coding with external controls

Vitotronic 100GC1

What is going on

Set coding 01 for the system type. Multi-boiler systems need plugs aVD and aVH wired.

Check in this order

  1. Single-boiler system set coding 01: 1 (factory setting). With a building automation system, only plug aVD is required.
  2. Set boiler water temperature to the minimum value.
  3. Multi-boiler system set coding 01: 3.
  4. Wire both plugs aVD and aVH. DHW tank and load-dependent cascade control must run through the building automation system.
  5. The boiler activation contact is essential. The lead boiler contact must stay constantly closed.

Applies to: Single and multi-boiler systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 installation manual, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.