Viessmann · Boiler troubleshooting

Connect several remote control units (Version 1)

Vitotronic 300 GW2

What is going on

Several Vitotrol remote controls are connected through a terminal box installed on site.

Check in this order

  1. Install a terminal box on site.
  2. Connect the control unit to the terminal box.
  3. Connect Vitotrol 1, Vitotrol 2 and Vitotrol 3 to the terminal box, following the wiring diagram.
  4. Keep each branch to the terminal box to a maximum of 15 m / 50 ft.
  5. Keep the total length of all KM BUS cables to a maximum of 50 m / 164 ft.

Applies to: Vitotrol remote controls on KM BUS

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300, Model GW2 installation and service instructions, p. 110. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.