Weil-McLain · Boiler troubleshooting

Example E - field wiring of master and shadow boilers

Evergreen Series 2

What is going on

Master boiler feeds zones 1 to 3 and the boiler isolation valve. Shadow boiler feeds the DHW circulator or DHW valve, zone 4, the bypass valve and the boiler isolation valve. Sensors go to the terminal blocks J16 and J17 with their commons, and the 120 VAC supply is through the service switch.

Check in this order

  1. Wire 120 VAC power and ground to each boiler through the service switch.
  2. Connect the zone thermostats (W, R, C) to the TT inputs listed in Table 6.
  3. Connect the boiler isolation valve (Item 17a) to the Primary Valve Control output on each boiler.
  4. Connect the bypass valve (Item 17b) to the Aux output on the shadow boiler and wire it so it closes when energized.
  5. Connect the DHW circulator or DHW valve to TT1 on the shadow boiler, and use a relay if its load is above the rating.
  6. Connect outdoor air, system supply and return sensors to J19 on the master.

Applies to: Example E, master and shadow 2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Evergreen Series 2 advanced manual, p. 38. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.