LON participant number and participant list update (single-boiler)

Vitotronic 100

What is going on

Single-boiler systems only. The LON communication module accessory must be fitted (see p. 111). The LON participant number is set with coding address 77 in coding level 1; factory setting is 77:1. Each number may be used only once in a LON BUS system. The control must be coded as error manager (79:1) to update the participant list, and all participants must be connected.

Check in this order

  1. Fit the LON communication module.
  2. Set the participant number with coding 77 in coding level 1.
  3. Code the control as error manager with coding 79:1 if it will manage the list.
  4. Press the two buttons shown on p. 87 together for about 2 seconds.
  5. Press D to start the participant check.
  6. Wait about 2 minutes for the participant list to update.

Applies to: Single-boiler systems with Vitotronic 100 GC1 on LON BUS

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.