Viessmann · Boiler troubleshooting
LON participant number and participant list update (single-boiler)
What is going on
Single-boiler systems only. The LON communication module accessory must be fitted (see p. 111). The LON participant number is set with coding address 77 in coding level 1; factory setting is 77:1. Each number may be used only once in a LON BUS system. The control must be coded as error manager (79:1) to update the participant list, and all participants must be connected.
Check in this order
- Fit the LON communication module.
- Set the participant number with coding 77 in coding level 1.
- Code the control as error manager with coding 79:1 if it will manage the list.
- Press the two buttons shown on p. 87 together for about 2 seconds.
- Press D to start the participant check.
- Wait about 2 minutes for the participant list to update.
Applies to: Single-boiler systems with Vitotronic 100 GC1 on LON BUS
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.