Viessmann · Boiler troubleshooting

Gas piping pressure test and leak check

Vitorond 200 VD2

What is going on

Protect the boiler from high test pressures and check the gas train for leaks after it is connected.

Check in this order

  1. Install a sediment trap or dirt pocket upstream of all gas controls.
  2. If the test pressure is above 14 in. w.c. (3.5 kPa), disconnect the boiler and its individual shut-off valve from the gas piping.
  3. If the test pressure is 14 in. w.c. (3.5 kPa) or less, close the boiler's individual manual shut-off valve to isolate it.
  4. Connect and size gas supply piping per local and national codes.
  5. Leak test with an approved liquid spray solution. Never use an open flame. Keep liquid off electrical parts and keep it away from the gas valve regulator and vent opening.
  6. Purge air from the gas line with an approved purge or vent to outdoors.
  7. Unions and the gas manifold were not factory tested, so a licensed gas fitter must complete a leak test during initial trial operation.

Applies to: VD2-320 to VD2-1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 installation manual, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.