Weil-McLain · Boiler troubleshooting
Zone valve zoning, variable primary flow with DHW
What is going on
Variable flow system with optional DHW piping shown in Figure 17.
Check in this order
- Install a system circulator sized for the variable flow and head.
- Install a flow/check valve on the boiler outlet to stop gravity circulation during DHW heating.
- Optionally add a bypass with a differential pressure valve between near-boiler supply and return. If used, place the System Supply sensor after the bypass.
- Install a flow switch if system flow could fall below the minimum flow in Figure 10.
- Connect DHW secondary connector piping no more than 8 pipe diameters apart.
Applies to: SVF 1500-3000 Series 1
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.