Viessmann · Boiler troubleshooting

Connect gateway at 24VAC to Vitodens 200 WB2B, HO1 or B2HA

Versatronik 505Versatronik 505D

What is going on

Wiring layout for a 24VAC gateway on Vitodens 200 WB2B, HO1 and B2HA.

Check in this order

  1. Refer to the boiler manual and install the LON communications card inside the boiler control.
  2. Plug the supplied 3 ft (91 cm) CAT-5 cable into the control and into the RJ45 socket inside the gateway.
  3. Connect the BACnet IP RJ45 communication cable to the gateway.
  4. Connect a field-supplied 24VAC power supply to the gateway.

Applies to: Vitodens 200 WB2B, Vitotronic 200 HO1, Vitodens 200 B2HA; 24VAC gateway

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 505 NR2/BACIP manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.