Viessmann · Boiler troubleshooting

Checking the expansion tank and system pressure

Vitodens 100-WB1HEB1KE

What is going on

Set the expansion tank precharge and the system fill pressure with the system cold, then record the minimum fill pressure.

Likely causes

  • Low water pressure from leakage shows up as a lower gauge reading

Check in this order

  1. Drain the boiler/system and reduce pressure until the gauge reads 0.
  2. If the tank nitrogen precharge is below the system static pressure, inflate the membrane to slightly above system pressure.
  3. Top up with water until fill pressure is higher than the expansion tank inlet pressure. With the system cold, fill pressure should be about 3 psig above static pressure.
  4. On first start-up, mark this reading as the minimum fill pressure on the gauge.
  5. Repair all leaks. A lower gauge reading later usually means water loss.
  6. Do the check with the system cold, with tank pressure matched to system fill pressure at about 60 F (15.6 C).

Applies to: Site expansion tank and system

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.