Wire remote alarm and additional heat demand contacts

ECO Tec Series 3

What is going on

Both are optional. Contact ratings are 24VAC or less and 0.5 A or less.

Check in this order

  1. For a remote alarm, connect J18 pins 4 and 5. The contact closes only when the boiler enters manual lockout.
  2. For an additional heat source, connect J18 pins 6 and 7 to call for heat from the other source.
  3. Set the control to use the additional heat demand contacts. See the control section (page 123) for setup.

Applies to: ECO Tec Series 3 all models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.