Check and clean the burner tube
What is going on
Cleaning or replacing the burner gauze and gaskets. Keep insulation fibres out of the combustion chamber.
Check in this order
- Dismantle the burner first (see burner dismantling guide).
- Undo the 6 screws on the insulation ring. Tighten to 13 lb.in (1.5 Nm) on reassembly.
- Remove the insulation ring.
- Unscrew the burner gauze assembly. Vacuum it or replace it. Tighten to 7.5 lb.ft (10 Nm) on reassembly.
- Replace all gaskets.
- Reassemble the burner tube and burner in reverse order. Tighten to 7.5 lb.ft (10 Nm).
- Make sure no insulation fibres stick to the burner tube and none fall into the combustion chamber.
Applies to: CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.