Viessmann · Boiler troubleshooting

Check and clean the burner tube

Vitocrossal 300 CA3B

What is going on

Cleaning or replacing the burner gauze and gaskets. Keep insulation fibres out of the combustion chamber.

Check in this order

  1. Dismantle the burner first (see burner dismantling guide).
  2. Undo the 6 screws on the insulation ring. Tighten to 13 lb.in (1.5 Nm) on reassembly.
  3. Remove the insulation ring.
  4. Unscrew the burner gauze assembly. Vacuum it or replace it. Tighten to 7.5 lb.ft (10 Nm) on reassembly.
  5. Replace all gaskets.
  6. Reassemble the burner tube and burner in reverse order. Tighten to 7.5 lb.ft (10 Nm).
  7. Make sure no insulation fibres stick to the burner tube and none fall into the combustion chamber.

Applies to: CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.