Check burner door gasket and burner gauze assembly

Vitodens 222-F

What is going on

Replace the burner gauze and gasket if damaged.

Check in this order

  1. Check burner door gasket A and cylinder burner assembly E for damage. Replace if needed.
  2. Remove the electrode block and ionization electrode B.
  3. Undo three retaining clips C and remove the thermal refractory ring D.
  4. Undo four Torx screws and remove burner gauze assembly E with gasket F.
  5. Fit a new gauze assembly and new gasket. Tighten to 31 lb.in (3.5 Nm).
  6. Refit refractory ring A and secure with clip C.
  7. Refit the electrode block and ionization electrode B and tighten to 40 lb.in (4.5 Nm).

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.