Viessmann · Boiler troubleshooting

Connecting external safety equipment (plug aBÖ)

Vitocrossal 300 CA3B Dual Fuel

What is going on

External safety devices such as pressure limiters are wired to plug aBÖ. Contacts must be potential-free and must not be live.

Likely causes

  • Live contacts on plug aBÖ cause short circuits or phase failure.

Check in this order

  1. Disconnect power to the control.
  2. Remove the jumper from the terminal pair in use: 17 (L) and 18 (L), 19 (L) and 20 (L), or 21 (L) and 22 (L).
  3. Connect the safety device to the freed pair.
  4. Confirm the safety circuit is normally closed.
  5. Make sure no live voltage is applied to the contacts.

Applies to: Minimum pressure limiter, maximum pressure limiter, other safety equipment

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.