Viessmann · Boiler troubleshooting
Connecting external safety equipment (plug aBÖ)
What is going on
External safety devices such as pressure limiters are wired to plug aBÖ. Contacts must be potential-free and must not be live.
Likely causes
- Live contacts on plug aBÖ cause short circuits or phase failure.
Check in this order
- Disconnect power to the control.
- Remove the jumper from the terminal pair in use: 17 (L) and 18 (L), 19 (L) and 20 (L), or 21 (L) and 22 (L).
- Connect the safety device to the freed pair.
- Confirm the safety circuit is normally closed.
- Make sure no live voltage is applied to the contacts.
Applies to: Minimum pressure limiter, maximum pressure limiter, other safety equipment
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.