Checking the room temperature sensor

Vitotronic 200-H

What is going on

The room temperature sensor measures the actual room temperature when the remote control cannot be installed in a suitable location. For connection, see pages 43 and 45.

Likely causes

  • Severe deviation between sensor reading and actual room temperature may point to a wiring or installation fault, or a faulty sensor.

Check in this order

  1. Disconnect the wires from the sensor.
  2. Measure the sensor resistance at terminals 9 and 13b.
  3. Compare the measured value with the actual room temperature shown on the display (scanning method on page 21).
  4. Check the installation if the deviation is severe.
  5. Replace the sensor if the installation is correct and the deviation is still severe.

Applies to: Room temperature sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H installation and service instructions, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.