Weil-McLain · Boiler troubleshooting

Gas valve adjustment at low fire

ECO Tec Series 3

What is going on

Adjust low fire only after confirming low fire RPM.

Check in this order

  1. Force LOW fire and let the boiler stabilize.
  2. Confirm the RPM against the table in Figure 125, 126 or 127.
  3. Remove the 4 mm Allen cap to reach the offset screw.
  4. If CO2 is high, turn the offset screw counter-clockwise in small steps.
  5. If CO2 is low, turn the offset screw clockwise in small steps.
  6. Continue until target CO2 is reached and confirm CO is within limits.
  7. Reinstall the 4 mm cap.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.