Viessmann · Boiler troubleshooting
Remove and reinstall the burner assembly
What is going on
Procedure to remove the burner for service and reinstall it with the correct torque.
Check in this order
- Switch the main power and the ON/OFF switch 8 to OFF. Slide the black control cover out to reach the switch.
- Shut off the gas valve.
- Fold down control unit A and remove cover B.
- Disconnect the cables from fan motor C, gas valve D, ionization electrode G, ignition module E and grounding wire F.
- Release gas supply pipe fitting H. A gasket sits between the gas valve and the fitting.
- Loosen the six Torx T-30 screws I and remove the burner.
- Check burner gasket J for damage. Replace the burner gasket about every 2 years.
- Do not lay the burner on its cylindrical tube or touch the tube mesh.
- Mount the burner and tighten the screws in a diagonal pattern to 132 lb.in (15 Nm).
- Fit the gas line connection with a new gasket and torque to 132 lb.in (15 Nm).
- Reconnect the electrical cables.
- Perform a gas leak test.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.