Burner control wiring with plug-in connection, VD2/VD2A/CT3
What is going on
Burner cables come with the Vitotronic. Connections are made to the counter plugs and to the burner, following applicable codes. The burner control circuit uses terminals 1, 2 and 3 for 2-stage or modulating operation.
Check in this order
- Disconnect power to the burner and the boiler control.
- Connect the 7-pole plug (fA) and the 3-pole plug (lÖ) to the matching counter plugs on the boiler control.
- Connect the 7-pole plug (fA) and the 3-pole plug (lÖ) to the burner.
- Check terminal use 1 from burner, 2 modulating down, 3 modulating up or 2nd stage ON.
- Confirm colour codes against the drawing (BK black, BN brown, BU blue).
Applies to: VD2/VD2A/CT3 controls with plug-in burner connection
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.