Viessmann · Boiler troubleshooting

Resetting the service display after maintenance

Vitotronic 100

What is going on

The service display is cleared by changing coding 24. If coding 24 is not reset, the service display comes back on Monday morning.

Likely causes

  • Service interval reached (flue gas temperature, burner hours or time interval).

Check in this order

  1. Set coding 24 to 1 if service is done before the service display appears, then set it back to 0.
  2. Reset the burner hours and burner starts with the reset button, then confirm.
  3. If needed, press and hold the two buttons together for about 4 seconds and reset the maximum flue gas temperature to the actual value.
  4. Set coding 24 back to 0 after maintenance.

Applies to: Vitotronic 100 GC1 boiler control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 98. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.