Viessmann · Boiler troubleshooting
Mixing valve motor turns in the wrong direction
What is going on
Mixing valve on an extension kit heating circuit does not respond correctly. The flow temperature rises or falls in the wrong way during the valve check.
Likely causes
- Motor rotation direction is wrong
- Mixing valve set is fitted incorrectly
Check in this order
- Disconnect main power before opening the boiler.
- Power up. The boiler runs a self-test during which the mixing valve opens and closes.
- Set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature. If it drops, the motor direction is wrong or the valve set is fitted incorrectly.
- To reverse the motor direction, remove the upper casing cover of the extension kit.
- At plug gS, swap the cores at terminals "|" and "~".
- Refit the casing cover.
Applies to: Extension kit for heating circuit with mixing valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA service instructions, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.