Rinnai · Boiler troubleshooting
Set up DHW recirculation through the PC board
What is going on
Enables and configures the DHW recirculation function using the left PC board button.
Check in this order
- Remove the boiler front panel and locate the PC board at the lower left side of the unit.
- Locate the left PC board button.
- Press and hold the button for five seconds to enter parameter setting.
- Set parameter 09 to b (YES) to enable DHW recirculation.
- Set parameters 12, 13 and 20 to the required settings for the piping and controls.
- Replace the front panel.
Applies to: I-Series Plus Condensing Combi Boiler
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 102. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.