Rinnai · Boiler troubleshooting

Twin pipe horizontal and vertical termination layout

I-Series Plus

What is going on

Termination spacing for twin pipe vertical and sidewall terminations, as shown on the layout figures.

Check in this order

  1. Keep the vertical termination at least 12 in (0.30 m) above grade or anticipated snow level.
  2. Keep the roof termination at least 12 in (0.30 m) minimum from the roof.
  3. Keep the combustion air intake at least 12 in (30 cm) from the exhaust and other openings as shown in the figures.
  4. Keep the sidewall exhaust at least 12 in (30 cm) from the wall and clear of the air intake by 8 in (20 cm) as shown on the sidewall figure.
  5. Do not place the combustion air intake in the area marked as not permitted for intake.

Applies to: Twin pipe termination installation

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.