Viessmann · Boiler troubleshooting
Mixing valve reduction for return temperature (Circuit Diagram 6)
What is going on
When return temperature falls below the minimum, the mixing valves are partly or fully closed via sensor T1.
Likely causes
- Return temperature below required minimum
Check in this order
- Verify sensor T1 is connected at plug aJA (4A: 1).
- Set coding 0d 1 so Therm-Control applies to downstream mixing valves.
- Size the common supply pump on 110% of the total supply output of the heating system.
Applies to: Circuit Diagram 6, common supply pump and low-pressure manifold
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.