Weil-McLain · Boiler troubleshooting
Assemble the pedestal floor stand
What is going on
Assemble the floor stand kit 383-800-245 and attach it to the boiler cabinet before setting the boiler upright.
Check in this order
- Set the boiler on its back, removing it from the styrofoam base.
- Lay the front section (A) flat. Install cross-supports (B) with the bent flange facing front, using eight 1/4 inch machine screws, nuts and washers. Hand tighten.
- Set the back section (F) on its back. Position the front section over it and fasten with eight 3/8 inch screws, nuts and washers. Use the holes for the specific model (80/110/150 or 199). Hand tighten only at this stage.
- Install the leveling legs into the rivets on the bottom of the stand and screw them all the way in. Do not overtighten.
- Hand install four 5/16 inch studs into the rivet nuts on the bottom of the boiler cabinet, with the short threaded end into the cabinet.
- Position the stand over the studs and against the cabinet bottom. Align the sides and curved corners with the cabinet and door. Secure with four 5/16 inch nuts without overtightening.
- Install the condensate trap assembly (see page 63) before lifting.
- Fully tighten all nuts, then lift the boiler upright with help.
- Level the boiler by turning the leveling legs with a flat head screwdriver.
- Install the floor stand door on the front section.
Applies to: Pedestal floor stand installations
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 15-16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.