Viessmann · Boiler troubleshooting

Application 5: how the low temperature and DHW circuits operate

Vitocrossal CU3A

What is going on

The system has a low temperature circuit on a 3-way mixing valve, a high temperature zone ZC1 (or ZC2), and an indirect DHW tank controlled by an aquastat. Space heating and DHW can run at the same time, so size the boiler for both. The HC2 mixing valve follows the boiler heating curve. The DHW aquastat call is read at the DE2 input, which switches on the 28/20 pump output. Pump P4 is not used when the air handler has an internal pump.

Check in this order

  1. Size the boiler for simultaneous space heating and DHW.
  2. Confirm the DHW aquastat is wired to DE2 so the 28/20 pump starts on a DHW call.
  3. If the air handler has no internal pump, make sure the 157 output is configured so P4 runs on a zone call.

Applies to: Application 5 layout

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300, CU3A Application Guide, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.