Viessmann · Boiler troubleshooting

Checking static gas pressure

Vitocrossal 300 CA3B Dual Fuel

What is going on

Static pressure is measured with the gas valve closed and then opened again. Do not remove the measuring connector screw.

Check in this order

  1. Close the gas shut-off valve.
  2. Loosen the screw in measuring connector A without removing it.
  3. Connect the pressure gauge at measuring connector A.
  4. Open the gas shut-off valve.
  5. Measure static pressure. It must not exceed 14 in w.c.
  6. Record the reading in the maintenance record (page 158).
  7. Make sure there is no open flame in the room during this work.
  8. Check for leaks with soap and water only. Never use a flame or purge gas into the combustion chamber.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.