Viessmann · Boiler troubleshooting

Reset the Service display after maintenance

Vitotronic 200

What is going on

Clears the Service message and resets the service interval. If service is done before 'Service' appears, set coding 24:1 first, then 24:0; this resets the operating hours and time interval to zero.

Check in this order

  1. If service is done before 'Service' shows, set coding 24:1 and then 24:0.
  2. Press the service scan button to start the service scan.
  3. Scroll through messages and acknowledge with 'Acknowledge: Yes'. The Service display goes off but the red fault indicator keeps flashing until coding 24 is reset.
  4. Press the button to end the service scan.
  5. After maintenance, reset coding 24:1 to 24:0. The red fault indicator goes off.
  6. If coding 24 is not reset, the Service display returns at 07:00 on Monday.
  7. Reset burner operating hours, starts and fuel consumption.
  8. Press the two buttons together for about 4 seconds, then reset max flue gas temperature to the current value.

Applies to: Vitotronic 200 KW2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 service instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.