Viessmann · Boiler troubleshooting

Fixed high limit adjustment (JUMO 100 ºC version)

Vitotronic 300

What is going on

Same purpose as the Etheco/EGO adjustment, for the JUMO limit. Step order is shown in the manual graphic, which is not readable in the extracted text.

Check in this order

  1. Remove the fuse, then follow the numbered steps in the manual illustration (steps 1 to 6).
  2. Set the fixed high limit to 100 ºC / 212 ºF.
  3. Keep the adjustable high limit at or below 167 ºF / 75 ºC.
  4. Check the box in the Vitotronic 300 service instructions.

Applies to: Vitotronic 300 fixed high limit (JUMO)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 installation instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.