Direct exhaust: combustion air from boiler room

Ultra Series 4

What is going on

Direct exhaust boilers draw combustion air from the boiler room through openings to outside or to other spaces, so the room must not have contaminated air.

Likely causes

  • Contaminated air in the boiler room
  • Exhaust fans creating negative pressure in the room
  • Undersized air openings when other appliances share the space

Check in this order

  1. Check that the boiler room will not contain contaminated air before using room air.
  2. Size combustion air openings for all appliances in the room, including exhaust fans and air movers.
  3. Make sure the room is not under negative pressure unless all appliances are direct vent.
  4. Count louver and grille reduction when sizing openings (free area).
  5. Follow Figure 96 sizing and the Massachusetts instructions on page 65 when they apply.

Applies to: Ultra boilers, direct exhaust sidewall or vertical

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 83-84. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.