Water chiller piping, primary/secondary
What is going on
For systems using a chilled water loop. The chiller must be piped in parallel with the boiler, and valves must keep chilled medium out of the boiler.
Check in this order
- Pipe the chiller in parallel with the boiler, as in Figure 19.
- Install valves that prevent chilled medium from entering the boiler.
- Install a separate circulator for the chilled water loop if the heating zones use circulators.
- Install a check valve and a balancing valve in the chilled loop as shown.
- Install a flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
- If the boiler feeds coils in air handlers that can see refrigerated air, use flow control valves or other automatic means to stop gravity circulation during cooling.
- If antifreeze is used, check its effect on circulator sizing and DHW performance. Use only antifreeze listed on p. 131.
Applies to: SVF 500/600 boilers in systems with a water chiller
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.