Viessmann · Boiler troubleshooting
LON daisy chain wiring to Vitotronic NR2
What is going on
The Versatronik 503 connects into the Vitotronic NR2 LON daisy chain through one of its two RJ45 (8P8C) jacks. Both jacks are linked internally, so either can be used. If the module is at the end of the bus, a LON end resistor (not supplied) goes into the open jack.
Check in this order
- Connect the LON cable from the previous device to one RJ45 jack on the Versatronik 503.
- Connect the next device in the chain to the other RJ45 jack, or leave it open if this is the last device.
- If the module is at the end of the bus, fit a LON end resistor (supplied separately) in the unused jack.
Applies to: Versatronik 503 LON connection
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 503 NR2/Analog Bridge installation and operating instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.