Weil-McLain · Boiler troubleshooting
Ignition safety shutoff device check
What is going on
Confirm the ignition system safety device locks out when there is no gas. The control makes one retry before lockout, per ASME CSD-1.
Check in this order
- After installation, turn the boiler off.
- Shut the manual gas valve downstream of the gas valve.
- Turn the boiler on. Ignition starts but the burner will not light.
- Confirm the boiler locks out after a set time: the display turns red and a solid red alarm shows.
- Clear the lockout by selecting <RESET CONTROL> in the red box.
- Open the manual gas valve to restore fuel.
Applies to: Ignition safety device verification
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 100. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.